Heat-shrinkable Tube

MPG series 10kV&35kV thermal shrinkable busbar protective bushing

Major performance indexes of MPG series thermal shrinkable busbar protective bushing

·Hardness(Shore A):<80·Tensile strength(Mpa):>12.0
·Density(kg/m³):1.15×10³·Elongation at break(%):>400
·Water absorption(%):<0.5·Breakdown strength(kV/mm):≥25
·Full shrinking temperature(℃):130±5·Volume resistivity(Ω:cm)>1×1014
·Radial shrinking ratio(%):>50·Oxygen index:≥30
·Axial shrinking ratio(%):<5.0·Eccentricity(%):<30


Comparison between earth and phase distance before and after the use of MPG series

System voltage

(kV)

Ordinary insulation distance
(mm)
Insulation distance after using MPG10 seriesInsulation distance after using MPG35 series
To the earth (mm)Between phase (mm)To the earth (mm)Between phase (mm)
1012080705040
2222016012010575
35320//200150

Note: Information in the above table is for reference only. The actual data may vary due to the power distribution system and environment.


ModelApplicable
busbar width
(mm)
Dimension before shrinking
(mm)
Dimension after shrinking
(mm)
Internal diameterWall thicknessInternal diameterWall thickness
10kV MPG2520~3025±1.01.0±0.2102.2±0.2
10kV MPG3030~4030±1.01.0±0.2132.2±0.2
10kV MPG4040~5040±1.01.0±0.2152.2±0.2
10kV MPG5050~6050±2.01.2±0.2202.5±0.2
10kV MPG60/6560~7065±2.01.2±0.2242.5±0.2
10kV MPG8080~10080±3.01.2±0.3322.5±0.2
10kV MPG100100~120100±4.01.2±0.3402.5±0.2
10kV MPG120150120±4.01.2±0.3482.7±0.3
10kV MPG150200150±4.01.2±0.3602.7±0.3
10kV MPG180max180±5.01.2±0.3702.7±0.3
10kV MPG210max210±5.01.2±0.3802.7±0.3
35kV MPG3030~4030±1.01.5±0.3133.0±0.3
35kV MPG4040~5040±1.01.5±0.3153.0±0.3
35kV MPG5050~6050±2.01.5±0.3203.0±0.3
35kV MPG60/6560~7065±2.01.5±0.3243.0±0.3
35kV MPG8080~10080±3.01.6±0.3323.2±0.3
35kV MPG100100~120100±4.01.6±0.3403.2±0.3
35kV MPG120150120±4.01.6±0.3483.2±0.3
35kV MPG150200150±4.01.6±0.3603.2±0.3
35kV MPG180max180±5.01.6±0.3703.2±0.3
35kV MPG210max210±5.01.6±0.3803.2±0.3


Share: